Question

How do I work with +Active Air fan ?

 Answer 


The fan must run at a minimum speed of 40%.

The Active Air fan is used in the following situations:




In the example above the fan speed is from 40 to 100% when the greenhouse temperature is from 21 (= 20 +1) to 27 (= 20 + 1 + 6) °C.
In this case we first try to cool the greenhouse by using the outside air valve and after that by using the fans.




    • Related Articles

    • EN - How to work with +Active Air overpressure

      Question How do I work with +Active Air overpressure?  Answer  The Active Air overpressure is used in the following situations: In these situations the maximum overpressure is 15 Pa (in practice between 10 and 15). During recirculation a minimum ...
    • EN - How to work with +Active Air dehumidification

      Question How do I work with +Active Air dehumidification?  Answer  The outside air valve and the fans can be used during dehumidification. They both will start at minimum position. The dehumidification capacity has to be entered by the grower (normal ...
    • EN - How to work with +Active Air valve

      Question How do I work with +Active Air valve?  Answer  The Active Air valve is used in the following situations: In the example above the valve is opened from 0 to 100% when the greenhouse temperature is from 20 to 22 (=20 + 2) °C. With the ...
    • EN - How to work with +Active Air cooling

      Question How do I work with +Active Air cooling?  Answer  The pad wall can be controlled in 5 stages by the cooling program. In the example above the cooling is starting when the greenhouse temperature is higher than 22 °C. With the influence ...
    • EN - How to work with +Active Air in a (semi) closed greenhouse

           Question How to work with +Active Air in a (semi) closed greenhouse?  Answer  The climate settings: The standard settings ventilation temperature leeside and windside are set to 35 °C and are hidden. Cooling 1 can be a pad wall and cooling 2 can ...