EN - How to work with +Active Air overpressure
Question
How do I work with +Active Air overpressure?
Answer
The Active Air overpressure is used in the following situations:
In these situations the maximum overpressure is 15 Pa (in practice between 10 and 15).
During recirculation a minimum overpressure of 8 Pa (in practice between 5 and 10).
A precontrol depending on fan speed and outside air valve opening.
An "overpressure control: influence" is calculated which can be used to open the overpressure windows.
This influence can also be used to close the outside air valve.
This influence can also be used to reduce the fan speed.
Related Articles
EN - How to work with +Active Air valve
Question How do I work with +Active Air valve? Answer The Active Air valve is used in the following situations: In the example above the valve is opened from 0 to 100% when the greenhouse temperature is from 20 to 22 (=20 + 2) °C. With the ...
EN - How to work with +Active Air fan
Question How do I work with +Active Air fan ? Answer The fan must run at a minimum speed of 40%. The Active Air fan is used in the following situations: In the example above the fan speed is from 40 to 100% when the greenhouse temperature is from ...
EN - How to work with +Active Air in a (semi) closed greenhouse
Question How to work with +Active Air in a (semi) closed greenhouse? Answer The climate settings: The standard settings ventilation temperature leeside and windside are set to 35 °C and are hidden. Cooling 1 can be a pad wall and cooling 2 can ...
EN - How to work with +Active Air cooling
Question How do I work with +Active Air cooling? Answer The pad wall can be controlled in 5 stages by the cooling program. In the example above the cooling is starting when the greenhouse temperature is higher than 22 °C. With the influence ...
EN - How to work with +Active Air heating
Question How do I work with +Active Air heating? Answer The Active Air heating is used in the following situations: The computed temperature of the heating element is between the minimum and maximum temperature. The pump is switched on when the ...