IIVO - Troubleshooting Aspirator box

IIVO - Troubleshooting Aspirator box

Greenhouse temperature is not measured properly with a dry/wet bulb aspirator box

  1. At a distance (online)
    1. Carefully read the installation manual on the PartnerWiki
    2. Check whether real time values are received in I/O CONFIGURATION
    3. Check whether the matrix is correct and no incorrect offset has been entered
    4. Check whether input is linked to the correct software

  2. On sight (local presence)
    1. Check the location of the aspirator box

    2. Check maintenance of the aspirator box

    3. Check the resistance value of the sensor with a universal meter (500 ohms at 0°C; +2 ohms per °C)

    4. Check the current value from the transmitter with a universal meter
        
    5. Check the led of the measuring channel (off=ok, on=not connected/not correct connected)

    6. Check the current value of the transmitter on the Data Connector with a universal meter
    7. If necessary, try a different measuring channel
  3. If necessary, inform the customer of the maintenance and location of the aspirator box

    • Related Articles

    • EN - 740600 - Aspirator box dry & wet bulb

         This article is only for Hoogendoorn Partners Question How to connect the aspirator box?  Answer  Read the attached installation and service manual. Click this link to see how to calibrate the aspirator box Click this link to read how to do ...
    • EN - How to switch off the fan in the aspirator box while using sulphur pots

         Question When you are burning sulphur to prevent mildew then it is highly recommanded to switch off the fan of the aspirator box. Otherwise the inside of the aspirator box becomes nasty and the sulfur affects the sensors which drastically shortens ...
    • EN - How an aspirator box works

           Question There is an aspiratox box installed. How does the aspirator box work?  Answer  The greenhouse temperature can be measured by an aspirator box. Inside the aspirator box there is a PT500 sensor. This sensor is made of Platinum (PT) and ...
    • IIVO - Watchdog relais Finder 86

      Only 1 watchdog per IIVO control station Carefully read the installation manual on the PartnerWiki Check the DIP switches on the timer module Set the blue potentiometer for the time to approx. 35 sec. Click the watchdog relay on the DIN rail in the ...
    • EN - How to calibrate an aspirator box

         This article is only for Hoogendoorn Partners Question How can I calibrate an spirator box?  Answer  Watch the video below how to calibrate the aspirator box: The calibration must be done in Access level: Service. 1. Double click on Aspirators 2. ...