EN - How to start irrigation on higher radiation sum only first cycle

EN - How to start irrigation on higher radiation sum only first cycle

    
Question

The grower wants that the first irrigation cycle starts when the radiation sum reaches 120 J/cm2.
The other cycles have to start when the radiation sum reaches 100 J/cm2.

How to start irrigation on higher radiation sum only first cycle?

 Answer 

Add an influence of "number of starts" to the radiation sum setting.
The irrigation starts when the radiation sum is higher than 120 J/cm2.
When the number of starts is 1 or higher than the irrigation starts when the radiation sum is higher than 100 J/cm2.
 

    • Related Articles

    • EN - Adjust irrigation drip cycle size on cloudy day compared to sunny day

                                                                                                                                                               Question Do you recognize this? You want to reduce the watering on a dark (cloudy) day, if it ...
    • EN - How to start irrigation based on radiation sum

         Question How to start irrigation based on radiation sum  Answer  The picture below shows the recipes settings. unit phase 2 supply phase 2 supply time: ViP The supply time is 3 minutes for every cycle. EC control EC value: ViP The EC value is set ...
    • EN - How to start irrigation manually

         Question How to start irrigation manually  Answer  The picture below shows the crop section settings. Choose the option "direct manual start" in the setting "start cycle" to start an irrigation cycle manually.
    • EN - iSii compact: How to set up the Irrigation Strategy

         Question How to set up the Irrigation Strategy?  Answer  The setpoints for irrigation can be found as follows: . Before the irrigation can start, valves must be connected. Hand start An irrigation cycle is started by hand as follows: Click in the ...
    • EN - How to start irrigation based on time

         Question How to start irrigation based on time  Answer  The picture below shows the recipes settings. unit phase 2 supply phase 2 supply time: ViP The supply time is 3 minutes for every cycle. EC control EC value: ViP The EC value is set to 1.5 pH ...