EN - How to use the vents to control too high humidity

EN - How to use the vents to control too high humidity

  
  
Question

How to use the vents to control humidity?



 Answer 


There is a special vent setting for humidity control: "lee side vent position: humidity".
With this setting it is possible to open the vent a little bit when the relative humidity (RH) is too high or the humidity deficit (HD) is too low.




Example 1: RH control



The vents start to open if the relative humidity is 5% higher than the set RH (in greenhouse climate settings).
If the RH is 10% higher than the set RH the vents will be 10% open.

For example when the set RH is 75%
 measured RH (%)
vent position (%)
79
0
80
0
81
2
82
4
83
6
84
8
85
10
86
10


Example 2: HD control



The vents start to open if the humidity deficit is 1 g/m3 lower than the set HD (in greenhouse climate settings).
If the HD is 2 g/m3 lower than the set HD the vents will be 10% open.

For example when the set HD is 3,5 g/m3
 measured HD (g/m3)
vent position (%)
3,6
0
3,5
0
3,0
2,5
2,5
5
2,0
7,5
1,5
10
1,4
10




    • Related Articles

    • EN - How to use the heating to control too high humidity

            Question How to use the heating to control too high humidity?  Answer  The setting for humidity control is: "circuit pipe minimum". With this setting it is possible to heat up the pipes when the relative humidity (RH) is too high or the ...
    • EN - How to use the vents to control too high CO2

            Question How to use the vents to control CO2?  Answer  The setting for CO2 control is: "lee side vent position minimum". With this setting it is possible to open the vent a little bit when the CO2, which is coming from the soil, is too high. ...
    • EN - How to use the vents to control too low humidity

         Question How to use the vents to control too low humidity?  Answer  The picture below shows the greenhouse climate settings. You can select the first 3 settings like this: ​ Here you see the 3 selected settings in 1 picture: When the relative is ...
    • EN - 025930 - How to use +PAR module?

      Question I have a PAR sensor in the greenhouse and the software module +PAR. How to use the +PAR module? Answer The iSii + PAR module is optional from version 3.3.3.1 or higher. With this module you can control the PAR value under the (partly) closed ...
    • EN - How to use +TO Control module ?

      Question How to use +TO Control module ? Answer This module assumes the relationship between radiation sum and 24-hour temperature. In +TO Control 1.0 (from iSii version 2) the control is based on average temperature per several days. In the setting ...