EN - iSii compact: How to set up the Soil heating control
Question
How to set up the Soil heating control?
Answer
The setpoints for the soil heating can be found as follows:
The measured and target soil temperature.
The pipe temperature is calculated based on the deviation between measured and target soil temperature.
Example:
The calculated P-value during decreasing bottom temperature.
Soil temperature °C | Calculated P-value °C |
20 | 20 |
18 | 28 |
16 | 36 |
14 | 44 |
12 | 52 |
10 | 60 |
8 | 60 |
The pump is switched on when the calculated pipe is higher than the setpoint “pipe temperature: pump ON”.