EN - Where to mount the sensors in a heat storage tank
Where to mount the sensors in a heat storage tank?
Details of the tank:
- 12 meters high
- capacity of 4,800 m3
- diameter is 22.6 m
- 13 sensors
By default, if we recommend it, we take 10% of the total height of the tank from the top as an empty area.
So the first sensor is 1.20 meters from the edge (not from the highest point), so that you always have some water above the sensor.
We also do the same at the bottom, so that you always have some water left under the sensor.
The remaining 11 sensors are linearly distributed.
Distribute the remaining 11 sensors as follows:
Remark: In this example, it is assumed that the spray pipes are mounted around 5% of the top and bottom of the tank.
.
The transmitters of the sensors are mounted in a separate connection box:
740570 Tank sensor connection box
Related Articles
EN - How to do maintenance on sensors
Question How to do maintenance on sensors? Answer Take a look to the attached schedule.
NL - Hoe onderhoud je sensors
Vraag Hoe onderhoud je sensors? Antwoord Bekijk het bijgevoegde schema.
EN - How to connect the iSii heat demand to an external system
This article is only for Hoogendoorn Partners Question How to connect the iSii heat demand to an external system? Answer 1. Connect all the heating circuits to a transport control in the iSii 2. You can connect the “transport: actuations” to a ...
NL - Waar monteer je de sensoren in een warmte opslag tank
Vraag Waar monteer je de sensoren in een warmte opslag tank? Antwoord Gegevens van de tank: - 12 meter hoog - inhoud van 4.800 m3 - diameter is 22,6 m - 13 sensoren Standaard, als wij het adviseren, nemen we 10% van de totale hoogte van de tank ...
EN - How to mount Jumo EC sensors?
How to mount Jumo EC sensors? See below the general recommendations of Jumo. 1. The ideal mounting: 2. Avoid dead zones or places where air can accumulate: 3. Avoid areas where air can remain. For example, at the end of a pipe: 4. Avoid areas where ...